Product Overview
Product Details
Data Download
Related Products
General
YCS8-S series is applicable to photovoltaic power generation system. When surge overvoltage occurs in the system due to lightning stroke or other reasons, the protector immediately conducts in nanosecond time to introduce the surge overvoltage to the earth, thus protecting the electrical equipment on the grid.
Conatct Us
● T2/T1+T2 surge protection has two types of protection, which can can meet Class I (10/350 μS waveform) and Class II (8/20 μS waveform) SPD test, and voltage protection level Up ≤ 1.5kV;
● Modular, large-capacity SPD, maximum discharge current Imax=40kA;
● Pluggable module;
● Based on zinc oxide technology, it has no power frequency aftercurrent and fast response speed, up to 25ns;
● The green window indicates normal, and the red indicates a defect, and the module needs to be replaced;
● Dual thermal disconnection device provides more reliable protection;
● Remote signal contacts are optional;
● Its surge protection range can be from power system to terminal equipment;
● It is applicable to direct lightning protection and surge protection of DC systems such as PV combiner box and PV distribution cabinet.
YCS8 | — | S | I+II | 40 | PV | 2P | DC600 | / |
Model | Types | Test category | Maximum discharge current | Use category | Number of poles | Maximum continuous working voltage | Functions | |
Photovoltaic surge protective device | /: Standard type S: Upgraded type | I+II: T1+T2 | 40: 40KA | PV: Photovoltaic/ direct-current |
2: 2P | DC600 | /: Non communication R: Remote communication |
|
3: 3P | DC1000 | |||||||
Dc1500 (Only type S) |
||||||||
II: T2 | 2: 2P | DC600 | ||||||
3: 3P | Dc1000 | |||||||
Dc1500 (Only type S) |
Model | YCS8 | ||||
Standard | IEC61643-31:2018; EN 50539-11:2013+A1:2014 | ||||
Test category | T1+T2 | T2 | |||
Number of poles | 2P | 3P | 2P | 3P | |
Maximum continuous working voltage Ucpv | 600VDC | 1000VDC | 600VDC | 1000VDC | |
Maximum discharge current Imax(kA) | 40 | ||||
Nominal discharge current In(kA) | 20 | ||||
Maximum impulse current limp(kA) | 6.25 | / | |||
Voltage protection level Up(kV) | 2.2 | 3.6 | 2.2 | 3.6 | |
Response time tA(ns) | ≤25 | ||||
Remote and indication | |||||
Working status/fault indication | Green/red | ||||
Remote contacts | Optional | ||||
Remote terminal | AC | 250V/0.5A | |||
switching capability | DC | 250VDC/0.1A/125VDC 0.2A/75VDC/0.5A | |||
Remote terminal connection capability | 1.5mm² | ||||
Installation and environment | |||||
Working temperature range | -40℃-+70℃ | ||||
Allowable working humidity | 5%…95% | ||||
Air pressure/altitude | 80k Pa…106k Pa/-500m 2000m | ||||
Terminal torque | 4.5Nm | ||||
Conductor cross section(maximum) | 35mm² | ||||
Installation method | DIN35 standard din-rail | ||||
Protection degree | IP20 | ||||
Shell material | Fire-proof level UL 94 V-0 | ||||
Thermal protection | Yes |
Note: 2P can be customized other voltage
Model | YCS8-S | ||||||
Standard | IEC61643-31:2018; EN 50539-11:2013+A1:2014 | ||||||
Test category | T1+T2 | T2 | |||||
Number of poles | 2P | 3P | 3P | 2P | 3P | 3P | |
Maximum continuous working voltage Ucpv | 600VDC | 1000VDC | 1500VDC | 600VDC | 1000VDC | 1500VDC | |
Maximum discharge current Imax(kA) | 40 | ||||||
Nominal discharge current In(kA) | 20 | ||||||
Maximum impulse current limp(kA) | 6.25 | / | |||||
Voltage protection level Up(kV) | 2.2 | 3.6 | 5.6 | 2.2 | 3.6 | 5.6 | |
Response time tA(ns) | ≤25 | ||||||
Remote and indication | |||||||
Working status/fault indication | Green/red | ||||||
Remote contacts | Optional | ||||||
Remote terminal | AC | 250V/0.5A | |||||
switching capability | DC | 250VDC/0.1A/125VDC 0.2A/75VDC/0.5A | |||||
Remote terminal connection capability | 1.5mm² | ||||||
Installation and environment | |||||||
Working temperature range | -40℃-+70℃ | ||||||
Allowable working humidity | 5%…95% | ||||||
Air pressure/altitude | 80k Pa…106k Pa/-500m 2000m | ||||||
Terminal torque | 4.5Nm | ||||||
Conductor cross section(maximum) | 35mm² | ||||||
Installation method | DIN35 standard din-rail | ||||||
Protection degree | IP20 | ||||||
Shell material | Fire-proof level UL 94 V-0 | ||||||
Thermal protection | Yes |
Note: 2P can be customized other voltage
Failure Protection Device
The surge protective device includes a built-in failure protection mechanism. In the event of overheating or malfunction, this mechanism automatically isolates the device from the power supply while providing a visible status indicator.
The status window displays green under normal operation and switches to red when a failure occurs.
Alarm Signaling Feature with Remote Contacts
The device can be configured with optional remote signaling contacts, offering both normally open and normally closed configurations. During normal operation, the normally closed contacts remain active. If any module of the device experiences a fault, the contacts will switch states—closing the normally open circuit and activating an alarm signal to notify of the issue.
YCS8
YCS8-S
YCS8-S DC1500