Product Overview
Product Details
Data Download
Related Products
General
Photovoltaic fuse YCF8-□ PVS series is applicable to DC distribution lines with rated voltage not exceeding DC1500V, rated current not exceeding 50A and rated short circuit capacity not exceeding 50kA; It is used for line overload and short circuit protection. It is mainly used in energy storage systems and solar photovoltaic combiner boxes as short circuit and overload protection for solar photovoltaic power generation devices, batteries and other semiconductor devices.
Standard: IEC 60269-6 UL248-19
Conatct Us
YCF8 | - | 63 | PVS | DC1500 |
Model | Shell frame | Product type | Rated Voltage | |
Fuse | 63 | PVS:Photovoltaic DC sailboat | DC1500V |
Model | YCF8-63PVS | |
Fuse size(mm) | 10 ×85 | 14 ×85 |
Rated working voltage Ue(V) | DC1500 | |
Rated insulation voltage Ui(V) | DC1500 | |
Rated short-circuit breaking capacity (KA) | 20 | |
Operating level | gPV | |
Standard | IEC60269-6, UL4248-19 | |
Number of poles | 1P | |
Installation method | TH-35 Din-rail installation | |
Operating environment and installation | ||
Working temperature | -40℃≤X≤+90℃ | |
Altitude | ≤2000m | |
Humidity | When the maximum temperature is+40℃, the relative humidity of the air shall not exceed 50%, and higher humidity can be allowed at lower temperatures, For example +90% at 25℃ . Special measures shall betaken for occasional condensation due to temperature changes; | |
Installation environment | In a place where there is no explosive medium and the medium is not enough to corrode metal and damage insulation gas and conductive dust. | |
Pollution degree | Level 3 | |
Installation category | III |
Fuse(Base) | Fuse | ||
Model | Model | Current rating | Voltage |
YCF8-63PVS DC1500 | YCF8-1085 | 2, 3, 4, 5, 6, 8, 10, 15, 16, 20, 25, 30, 32 | DC1500 |
YCF8-1485 | 30-50 |
YCF8 | - | 1085 | 25A | DC1500 |
Product name | Size | Rated current | Rated Voltage | |
Fuse link | 1085: 10×85(mm) | 2-32A | DC1500V | |
1485: 14×85(mm) | 40-50A |
Model | YCF8-1085 | YCF8-1485 |
Rated current In(A) | 2-32A | 40-50A |
Fuse size | 10×85 | 14×85 |
Rated working voltage Ue(V) | DC1500 | |
Rated short-circuit breaking capacity (KA) | 20 | |
Time constant(ms) | 1-3ms | |
Operating level | gPV | |
Standard | IEC60269-6, UL248-19 |
The agreed time and current of the fuse “gPV”
Rated current of the fuse “gPV” (A) | Agreed time (h) | Agreed current | |
Inf | If | ||
In ≤63 | 1 | 1.13In | 1.45In |
63<In ≤160 | 2 | ||
160<In ≤400 | 3 | ||
In>400 | 4 |
Model | Rated current | Joule integral I²T(A²S) | |
(A) | Pre-arcing | Total | |
YCF8-1085 | 2 | 4 | 8 |
3 | 6 | 11 | |
4 | 8 | 14 | |
5 | 11 | 22 | |
6 | 15 | 30 | |
8 | 9 | 35 | |
10 | 10 | 98 | |
12 | 12 | 120 | |
15 | 14 | 170 | |
20 | 34 | 400 | |
25 | 65 | 550 | |
30 | 85 | 680 | |
32 | 90 | 720 | |
YCF8-1485 | 40 | 125 | 800 |
50 | 155 | 920 |
Base
Link
YCF8-□ □ PV series fuses have a rated operating voltage of DC1500V and a rated current of 80A. It is mainly used in the solar photovoltaic DC combiner box to break the line overload and short-circuit current generated by the current feedback of the photovoltaic components of the solar panel and the inverter, so as to protect the solar photovoltaic components. It is widely used in the circuit protection of electric drive system, power supply system and auxiliary system, and the fuse can also be selected in any other DC circuit as the circuit overload and short circuit protection of electrical components.
Standard: IEC60269, UL4248-19.
The fuse base is made of a plastic pressed shell with contacts and fuse-carrying parts, which are riveted and connected, and can be used as the supporting part of the fuse link of corresponding size. This series of fuses has the characteristics of small size, convenient installation, safe use and beautiful appearance.
YCF8 | - | 32 | X | PV | DC1500 |
Model | Shell frame | Functions | Product type | Rated Voltage | |
Fuse | 32: 1~32A | /:standard X: With display H: High base | PV: Photovoltaic/ direct-current |
DC1000V | |
63: 15~40A | /:non | DC1000V | |||
125: 40~80A | DC1500V |
Fuse holder | Assembly fuse |
YCF8-32 | YCF8-1038 |
YCF8-63 | YCF8-1451 |
YCF8-125 | YCF8-2258 |
Model | YCF8-32PV | YCF8-63PV | YCF8-125PV |
Specifications | /:standard X: With display H: High base |
/:standard |
/:standard |
Fuse size(mm) | 10 ×38 | 14 ×51 | 22 ×58 |
Rated working voltage Ue(V) | DC1000 | DC1500 | |
Rated insulation voltage Ui(V) | DC1500 | ||
Use category | gPV | ||
Standard | IEC60269-6, UL4248-19 | ||
Number of poles | 1P | ||
Operating environment and installation | |||
Working temperature | -40℃≤X≤+90℃ | ||
Altitude | ≤2000m | ||
Humidity | When the maximum temperature is+40℃, the relative humidity of the air shall not exceed 50%, and higher humidity can be allowed at lower temperatures, For example+ 90% at 25℃ Special measures shall betaken for occasional condensation due to temperature changes; | ||
Installation environment | In a place where there is no explosive medium and the medium is not enough to corrode metal and damage insulation gas and conductive dust. | ||
Pollution degree | Level 3 | ||
Installation category | III | ||
Installation method | TH-35 Din-rail installation |
The variable cross-section melt made of pure silver sheet (or silver wire winding) is soldered with low-temperature tin and packaged in a fusion tube made of high- strength porcelain. The fusion tube is filled with chemically treated and specially processed Process-treated high-purity quartz sand is used as the arc-extinguishing medium, and the two ends of the melt are firmly electrically connected with the contacts by electric welding.
YCF8 | - | 1038 | 25A | DC1500 |
Model | Size | Rated current | Rated voltage | |
Fuse | 1038: 10×38 | 1,2,3,4,5,6,8,10,15, 16,20,25,30,32 |
DC1000V | |
1451: 14×51 | 15,16,20,25,30, 32,40,50 |
DC1000V | ||
2258: 22×58 | 40,50,63,80 | DC1500V |
Model | YCF8-1038 | YCF8-1451 | YCF8-2258 |
Rated current In(A) | 1,2,3,4,5,6,8,10,12,15,
20,25,30,32 |
15,20,25,30,32,40,50 | 40,50,63,80 |
Specifications | /
X: With display H: High base |
/ |
/ |
Fuse size(mm) | 10×38 | 14×51 | 22×58 |
Rated working voltage Ue(V) | DC1000 | DC1000,DC1500 | |
Rated short-circuit breaking capacity (KA) | 20 | ||
Time constant(ms) | 1-3ms | ||
Operating level | gPV | ||
Standards | IEC60269-6, UL248-19 |
The agreed time and current of the fuse “gPV”
Rated current of
the fuse ”gPV” (A) |
Agreed time
(h) |
Agreed current | |
Inf | If | ||
In ≤63 | 1 | 1.13In | 1.45In |
63<In ≤160 | 2 | ||
160<In ≤400 | 3 | ||
In>400 | 4 |
Model | Rated current
(A) |
Joule integral I²T(A²S) | |
Pre-arcing | Total | ||
YCF8-1038 | 1 | 0.15 | 0.4 |
2 | 1.2 | 3.3 | |
3 | 3.9 | 11 | |
4 | 10 | 27 | |
5 | 18 | 48 | |
6 | 31 | 89 | |
8 | 3.1 | 31 | |
10 | 7.2 | 68 | |
12 | 16 | 136 | |
15 | 24 | 215 | |
16 | 28 | 255 | |
20 | 38 | 392 | |
25 | 71 | 508 | |
30 | 102 | 821 | |
32 | 176 | 976 | |
YCF8-1451 | 15 | 330 | 275 |
20 | 220 | 578 | |
25 | 275 | 956 | |
30 | 380 | 1160 | |
32 | 405 | 1830 | |
40 | 600 | 2430 | |
50 | 850 | 3050 | |
YCF8-2258 | 40 | 750 | 3450 |
50 | 1020 | 5050 | |
63 | |||
80 |
Base