Product Overview
Product Details
Data Download
Related Products
General
Cage type isolation switch YCISC8 series is suitable for DC power systems with rated voltage DC1200V and below and rated current 32A and below. This product is used for infrequent on/off, and can disconnect 1~2 MPPT lines at the same time. It is mainly used in the control cabinet, distribution box and combiner box of the photovoltaic power generation system, and is used for isolation of the DC power distribution system. The external waterproof performance of this product reaches IP66.
Standards: IEC/EN60947-3: AS60947.3, UL508i.
Conatct Us
● E type external installation can reach IP66 waterproof level at any angle;
● UV resistant and V0 flame retardant material;
● Contact silver plating, silver layer thickness reaches the highest standard in the industry;
● Arc extinguishing time(3ms);
● The bottom of the external box is equipped with a breather valve;
● Nonpolarity;
● Lockable in closed position;
● 4 installation modes optional.
YCISC8 | — | 32 | X | PV | P | 2 | MC4 | 13A | + | YCISC8-C |
Model | Rated current | With lock or not | Usage | Installation mode | Wiring mothod | Joint type | Rated current | Model | ||
Isolation switch | 32 | /: No lock X: With lock | PV: Photovoltaic/ direct-current | No: Din rail installation | 2\4\4B\ 4T\4S | /: No | DC1000 DC1200 | C: Terminal shield | ||
P: Panel installation | /: No | |||||||||
D: Door lock installation | M25: PG25 Waterproof joint M16: PG16 Waterproof joint | |||||||||
E: External installation | MC4: MC4 joint |
Note: The “Din rail installation” and “external installation” can only be with the lock.
Model | YCISC8-32PV | |||
Standards | IEC/EN60947-3:AS60947.3, UL508i | |||
Use category | DC-PV1, DC-PV2 | |||
Appearance | ||||
Din rail installation | Panel installation | Door lock installation | External | |
Wiring method | 2,2H,4,4T,4B,4S | /,M25,2MC4,4MC4 | ||
Shell frame grade | 32 | |||
Electrical performance | ||||
Rated heating current Ith(A) | 32 | |||
Rated insulation voltage Ui(V DC) | 1500 | |||
Rated working voltage Ue(V DC) | 1000V or 1200V | |||
Rated impulse voltage Uimp(kV) | 8 | |||
Rated short-time withstand current Icw(1s)(kA) | 1kA | |||
Rated short-time making capacity(Icm)(A) | 1.7kA | |||
Rated short circuit current(Icn) | 3kA | |||
Overvoltage category | II | |||
Polarity | No polarity, “+” and “-” polarity can be interchanged | |||
Switch knob position | 9 o’clock position off, 12 o’clock position on (or 12 o’clock position off, 3 o’clock position on) | |||
Service life | Mechanical | 10000 | ||
Electrical | 3000 | |||
Applicable environmental conditions and installation | ||||
Maximum wiring capacity (including jumper wires) | ||||
Single wire or standard(mm²) | 4-16 | |||
Flexible cord(mm²) | 4-10 | |||
Flexible cord (+ stranded cable end)(mm²) | 4-10 | |||
Torque | ||||
Tightening torque of terminal M4 screw(Nm) | 1.2-1.8 | |||
Tightening torque of upper cover mounting screw ST4.2 (304 stainless steel)(Nm) | 1.5-2.0 | |||
Tightening torque of knob M3 screw(Nm) | 0.5-0.7 | |||
Bottom wiring torque(Nm) | 1.1-1.4 | |||
Environment | ||||
Protection degree | IP20; External type IP66 | |||
Operating temperature(℃) | -40~+85 | |||
Storage temperature(℃) | -40~+85 | |||
Pollution degree | 3 | |||
Overvoltage category | III |
Type | 2-Pole | 4-Pole | 4-Pole with Input and Output on top | 4-Pole with Input and Output bottom | 4-Pole with Input on top Output bottom |
YCISC8-32 DC1000/DC1200 | 2 | 4 | 4T | 4B | 4S |
Contacts Wiring graph | |||||
Switching example |
Power distribution module DC switch(YCISC8-32XPV)
Panel mounting
Door-lock installation DC switch
External DC switch
The following current data IEC/EN60947-3:2009+A1+A2, AS60947.3, use category DC-PV1, DC-PV2
Model | Series | Wiring method | 300V | 600V | 800V | 1000V | 1200V | |||||
PV1 | PV2 | PV1 | PV2 | PV1 | PV2 | PV1 | PV2 | PV1 | PV2 | |||
YCISC8-32XPV □2 DC1000 | 1 | 2 | 32 | 32 | 32 | 32 | 32 | 16 | 16 | 9 | / | / |
YCISC8-32XPV □2 DC1200 | 1 | 32 | 32 | 32 | 32 | 32 | 16 | 16 | 9 | 13 | 9 | |
YCISC8-32XPV □4 DC1000 | 2 | 4 | 32 | 32 | 32 | 32 | 32 | 16 | 16 | 9 | / | / |
YCISC8-32XPV □4 DC1200 | 2 | 32 | 32 | 32 | 32 | 32 | 16 | 16 | 9 | 13 | 9 | |
YCISC8-32XPV □4S DC1000 | 1 | 4S | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | / | / |
YCISC8-32XPV □4S DC1200 | 1 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | |
YCISC8-32XPV □4B DC1000 | 1 | 4B | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | / | / |
YCISC8-32XPV □4B DC1200 | 1 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | |
YCISC8-32XPV □4T DC1000 | 1 | 4T | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | / | / |
YCISC8-32XPV □4T DC1200 | 1 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 |
Main contact | Voltage | DC1000 | DC1200 |
Rated thermal current Ithe | 32A | ||
Rated insulation voltage Ui | 1500V | ||
Contact spacing (per pole) | 8mm | ||
Rated working current Ie(DC-PV2) | |||
4 layers, only 2 layers in series, with two loads 1 2 | 300V | 32A | 32A |
600V | 32A | 32A | |
800V | 16A | 16A | |
1000V | 9A | 9A | |
1200V | / | 9A | |
4 layers, 4 layers in series, one load 1 2 3 4 | 300V | 32A | 32A |
600V | 32A | 32A | |
800V | 32A | 32A | |
1000V | 32A | 32A | |
1200V | / | 32A |
Type | |||
Number of poles | 4-pole | ||
Terminal name, main circuit | 1; 3; 5;7; 2; 4; 6; 8 | ||
Terminal type, main circuit | Screw terminal | ||
Cable cross-section | 4.0-16mm² | ||
Conductor type | 4-16mm (rigidity: solid or stranded) | ||
4-10mm Flexible | |||
Number of wires per terminal | 1 | ||
Preparation required for wire | Yes | ||
Stripping length (mm),main circuit | 8mm | ||
Tightening torque (M4), main circuit | 1.2~1.8N.m |